Chauvin Arnoux C.A. 6115 installasjonstester
Beskrivelse av varen
Tilstand: Som ny - Ikke synlig brukt
INSULATION (IEC/EN 61557- 2)
• Rated voltage: 100 V - 250 V - 500 V DC
• Range: 0.05...300 / 600 MΩ
• Resolution: 1kΩ...1MΩ
• Accuracy : +/- (6% measurement + 1 digit)
• Rated current: > 1 mA DC
• Short-circuit current: < 12 mA DC
EARTH (IEC/EN 61557- 5)
• Power supply: 95...145 V; 175...300 V AC
• Frequency: 15.3...17.5 Hz; 45...65 Hz
• Range: 0.15 Ω...10 kΩ
• Resolution: 0.01...10 Ω
• Accuracy: +/- (10% measurement + 3 digit)
• Method: only 1 auxiliary rod (earth to earth)
• Selective measurement of earth (one particular earth
out of several others in parallel) possible, with clamp..
• Values can be saved or printed at programmable
intervals.
RCD (IEC/EN 61557- 6)
• L-N-PE Voltage: 95...145 V; 175...300 V AC
• Frequency: 15.3...17.5 Hz; 45...65 Hz
• IΔn = 10-30-100-300-500 mA or 6...1000 mA
(in 1 mA increments)
• Trip-failure test: at 1/2 IΔn; Duration: 1000 ms
• Measurement of trip time: at IΔn, 2 IΔn (selective),
5 IΔn, 150 mA, 250 mA
Duration: 500 ms Resolution: 0.1 ms Accuracy: ± 2 ms
• Measurement of trip current / time:
0.5...1.033 IΔn ramp, in 3% increments
Duration of each increment: 200 ms
• Fault voltage: 1.5...100 V AC
CONTINUITY (IEC/EN 61557- 4)
• Test voltage: 18 V DC
• Rated I: > 200 mA to 10 Ω
• Range: 0.16 Ω...2 kΩ
• Resolution : 0.01...1 Ω
• Accuracy: +/- (5% measurement + 4 digit)
LOOP (IEC/EN 61557- 3)
• L-N-PE Voltage: 95...145 V; 175...300 V; 330...440 V AC
• Frequency: 15.3...17.5 Hz; 45...65 Hz
• Range: 0.08 Ω...200 Ω (resistance and impedance)
• Resolution : 0.001...0.1 Ω
• Accuracy: +/- (5% mesure + 3 digit)
• Short-circuit current calculation: 0.5 A...30 kA
• Patented “ALT” system: does not trip 30 mA RCD
• Values can be saved or printed at programmable
intervals.
PHASE ROTATION (IEC/EN 61557- 7)
• Voltage: 20...440 V AC
• Frequency: 15.3...450 Hz
CURRENT / VOLTAGE / FREQUENCY
• Current range: 4 mA...100 A with an MN 21 clamp and up
to 300 A with a C 103 clamp. Resolution: 1 mA...1 A
Accuracy : +/- (2% measurement + 1 digit)
• Voltage range: 10...440 V AC/DC Resolution: 1 V,
Accuracy: +/- (1% measurement + 1 digit)
• Frequency range: 15.3...450 Hz Resolution: 0.1...1 Hz,
Accuracy: +/- (0.1% measurement + 1 digit)
GENERAL SPECIFICATIONS
• Compliant with IEC 1010-1 standard Cat III 300 V
• Double insulation
• Memory holds 800 measurements
• RS232C Interface
• Programmable thresholds for each function
• NiMH battery + internal charger